Spectra Series™ Power Panelboards
Circuit Breakers and Modules
WARNING: Dan
g
er of electrical shock or in
j
ur
y
.
Turn
OFF
p
ower ahead of the
p
anelboard or
switchboard before workin
g
inside the
e
q
ui
p
ment or removin
g
an
y
com
p
onent. Do
not remove circuit
p
rotective devices or an
y
other com
p
onent until the
p
ower is turned
OFF.
General
These instructions apply to the following catalog numbers:
Circuit breaker modules AMC3KM and AMC2KM
Circuit breaker frames TKM, THKM, TK4V, TKL4V,
SKHA, SKLA, and SKPA
Installation
1. Phase balancing for two-pole devices in three-phase
systems. To balance the panelboard load, remove the
screws on the appropriate bus clip, reposition the bus
clip as shown in Figure 1, then install and tighten the
screws to 27–32 in-lb.
Figure 1. Repositioning the bus clip to balance the load.
2. Prepare the breaker module. Loosen the latch lock
screws and fully retract the rail latches. Line up the
guide fingers on both ends of the module with the
notches in the panelboard interior rails, as shown in
Figure 2.
Figure 2. Preparing the circuit breaker module for installation.
3. Install the module. Latch one side of the circuit
breaker module. Release the rail latch. Pivot the
module onto the bus bars and engage the second
latch. Release the rail latch. Tighten the rail latch
screws to 25 in-lb as shown in Figure 3. Allow no space
between units except as noted for type SKPA circuit
breakers in the Caution below.
CAUTION: When a t
yp
e SKPA circuit breaker is
to be mounted on a module ad
j
acent to an ADS
switch, leave a 1X (1
3
/8") s
p
ace between the
units. Use an APP1W
p
anel filler
p
late to close
the opening.
GEH5623 Installation Instructions R04
A & C Phase
As Received
A & B Phase
B & C Phase
Latch
Screw
Rail
Latch
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Installation

gSpectra Series™ Power PanelboardsCircuit Breakers and ModulesWARNING: Danger of electrical shock or injury.Turn OFF power ahead of the panelboard

Seite 2

Figure 3. Installing the circuit breaker module.4. Install the circuit breaker on the module.a. TKM and THKM circuit breakers used as maindevic

Seite 3

Figure 6. Securing the contact block to the studs and straps.c. SKHA, SKLA, and SKPA circuit breakers used asmain devices (lugs only on th

Seite 4 - Terminations

Attention – Procedure for AluminumTerminations1. Strip the insulation, being careful to not nick the wire.2. Clean the wire strands with a wire brush.