EntelliGuard® R Circuit Breaker Retrofill AKD-6 Installation ManualGeneral Electric AKD-6 Low Voltage Switchgear is a free-standing assembly of meta
9 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Mechanical Drawings Below is an
10 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 AKD-6—Compartment Interior Fig
11 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 5. AKD-6 Compartment Di
12 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 6. AKD6 Breaker Compart
13 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 7. Bus, Interior View
14 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Falling Object • Do not walk
15 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Remove Circuit Breaker from C
16 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Store Circuit Breaker If you
17 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Check Before Installing • It
18 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Rack Out Legacy or Existing CB
1 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Table of Content Preface ...
19 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 If the application requires in
20 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 8. Verify that the wire mark
21 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Typical wiring diagrams for t
22 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 11. AKD-6—Position Swit
23 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Install Door Interlock System
24 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 5. Insert the E-clips mention
25 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Install Neutral Rogowski Curre
26 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 17. 19-Pin Programmer D
27 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Install or Insert AKD-6 Retrof
28 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 21. AKD-6 Rails or Arms
2 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Store Circuit Breaker ...
29 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 13. As soon as the breaker is
30 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 23. Latching Inner Rail
31 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 28. As the breaker approaches
32 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Remove and Replace Existing Do
33 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 27. Prepare AKD-6—Compa
34 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Install Neutral Disconnect As
35 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 3. The existing neutral CT as
36 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Install 19-Pin Programmer Sec
37 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Figure 29. AKD-6—Slide the Inn
38 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Wiring Diagram for the AK/AKR
3 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Preface Hazards The following i
39 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Notes
GE Energy41 Woodford AvenuePlainville, CT 06062www.geindustrial.com© 2012 GE CompanyDEH-41548 02/12 imagination at work
4 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Warning This indicates a hazard
5 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Notice or Note This indicates i
6 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Related Publications Publicatio
7 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 Views General Electric AKD-6 Lo
8 EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12 History and Types AKD AK—Power