DEH40912 Installation Instructions
g
Record Plus
Molded Case Circuit Breaker
Accessories
Cable Operating Mechanism
Congratulations and thank
y
ou for choosing the
Record Plus™
family of current-limiting circui
t
breakers. This UL-listed handle operating
mechanism kits and cables are suitable for use with
the FC and FE circuit breaker series.
Record Plus™
circuit breakers are designed with a
full line of integrated accessories. All units use the
latest in integrated modular circuit breake
r
technolog
y
for flexibilit
y
in application and
maximizing the product’s utilization and
capabilities.
Record Plus™
circuit breakers are listed b
y
TION:
This product is NOT suitable for use
in equipment not specifically design to accept it.
Contact the equipment manufacturer for possible
equipment modifications.
ATTENTION:
Cet appareil nedoit pas etre
employe dans un equipement non specialement
adapte a cet effet. Contactez le constructeur
concernant les possibles modifications a apporter
a l'equipement.
CAU
W
arning: DANGER of electrical shock or injury.
Ensure ALL electrical power supplies are OFF
before installing or removing any devices. Do
not remove circuit protective devices until the
power is turned OFF. The breaker, trip unit, or
accessories MUST ONLY be installed and
serviced by QUALIFIED personnel. See NEMA
publication AB4.
A
vertissement: Danger contre les risques
d'électrocutions. S'assurer avant TOUTES
manipulations du disjoncteur que les différentes
sources d'alimentation sont en position OFF. Les
disjoncteurs, unités de protection, ou accessoires
doivent être installés par des personnes qualifiées
et habilitées. Ne pas retirer l’appariel de
protection avant que l’alimentation soit coupée.
Lira NEMA publication AB4.
Underwriters Laboratories to the UL489 standard
and the CSA Standard C22.2, No. 5. These circui
t
breakers are certified to EN 60947-2.
These accessories are also for use with our MAG
-
BREAK® motor circuit protectors, which meet the
same standards and are UL-recognized components
for use in motor applications. The
y
can also be used
w
ith our molded case switches, which are listed per
Underwriters Laboratories to the UL489 standard.
Record Plus™
circuit breakers and thei
r
accessories are designed and manufactured to
exceed our global customers’ high standards fo
r
reliability and quality.
Figure 1a.FCNBM
mounted on
FC circuit breaker
Figure 1b.FENBM
mounted on
FE circuit breaker
Figure 1. Cable operating mechanism mounted on
Record Plus™ circuit breakers.
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Record Plus

DEH40912 Installation Instructions g Record Plus ™ Molded Case Circuit Breaker Accessories   Cable Operating Mechanism Congratulations and

Seite 2

Step 1 – Unpack and Inspect Product Description Unpack the cable operator components andinspect for damage. Verify that all parts aresupplied, as

Seite 3 - Operating Mechanism

Step 2 – Install the Breaker Operating Mechanism 36-Inch Cable (SC3L) 48-Inch Cable (SC4L) This procedure is illustrated in Figure 2, Fi

Seite 4

  Figure 4a. Installing the circuit breaker operating mechanism on the FC breaker. Figure 5. End view of flange and door (right

Seite 5

Figure 8. Handle mechanism installation. Step 3 – Install the Handle Operating Mechanism Handle L, in. (mm) H

Seite 6 - Step 4 – Install the Cable

5. Attach the drive arm mechanism to the handle drive link with the connecting pin [11]. Secure with a retaining ring [12], as shown in Figure 8. 6.

Seite 7

Figure 9a. Installing the operating cable between the handle assembly and the breaker operating mechanism [23] [22] [21] [1] [Br

Seite 8 - – Operatio

Step 5 – Operation Normal Operation Move the handle to the ON position to close thebreaker or to the OFF position to open the breaker. Reset the Brea