Introduction
The Network Interlock provides a means of locking out a
circuit breaker to coordinate its operation with other
circuit breakers in the distribution network. When
activated by the EntelliGuard Messenger™, the Network
Interlock prevents the circuit breaker from closing. After
the EntelliGuard Messenger issues a reset signal, the
circuit breaker can be closed either remotely or locally.
The Network Interlock accessory includes a manual reset
lever to reset the device in the absence of a signal from the
EntelliGuard Messenger.
The Network Interlock contains a microswitch to remotely
indicate the state of the lockout and thus whether or not
the circuit breaker can be closed. The Network Interlock
kit (EGNTWKSFKIT) consists of the Network Interlock
module (EGNTWKSFRPLC), mounting plate, trip paddle
assembly, manual reset assembly, and hardware, as
illustrated in Figure 1. The catalog information for the
small frame Network Interlock kit and replacement
module is listed in Table 1.
Note: The Network Interlock kit is for use with
EntelliGuard
TM
circuit breakers installed in Entellisys™
Low Voltage Switchgear only.
Note: A Bell Alarm with Lockout and Network Interlock
cannot be installed concurrently in a circuit breaker.
Description
Catalog
Number
Voltage
Rating
60 Hz,
VAC
Inrush
current
A
Sealed
current
A
Complete Kit
(NI Module+
Mounting)
EGNTWKSFKIT
NI Module EGNTWKSFRPLC
120
6
1.43
Table 1. Catalog numbers and electrical ratings.
Figure 1. Network Interlock kit assembly (EGNTWKSFKIT).
Operation
The Network Interlock consists of a set solenoid, a reset
solenoid, and a status switch. The device connections to
the secondary disconnect are shown in Figure 2. When
voltage is applied across the set solenoid, the device locks
out the circuit breaker. Conversely, when voltage is applied
to the reset solenoid or when the manual reset button is
depressed, the Network Interlock allows the circuit breaker
to re-close.
Figure 2. Network Interlock connections to secondary disconnect.
(Contact shown in RESET state.)
g
EntelliGuard
TM
Power Circuit
BreakerAccessories
DEH41119 Installation Instructions R01
Network Interlock for 8002000 Ampere
Circuit Breakers
Trip Paddle
Assembly
Mounting plate
Manual Reset Assembly
Network Interlock
Module
(EGNTWKSFRPLC)
15
NI Set
Coil
20
16
21
19
NI Reset
Coil
NI Status
Contact
1
3
2
4
5
DEH41119 Installation Instructions R02
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Circuit Breakers

Introduction The Network Interlock provides a means of locking out a circuit breaker to coordinate its operation with other circuit breakers in the d

Seite 2 - OFF, le

WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing springs. AV

Seite 3

Figure 3. Fastening the Network Interlock module to the mounting plate. Figure 4. Mounting the trip paddle

Seite 4

Figure 7. Mounting the manual reset assembly Figure 8. Wire routing from the Network Interlock to the secondary disconne

Seite 5 - Module Replacement

WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing springs. AVER

Seite 8

These instructions do not cover all details or variations in equipment nor do they provide for every