Follow these steps:
1. Remove the Keypad (F) or Blind Cover
2. Remove the Terminal Cover (G)
3. Remove the Cable Decoupling Plate (H) and the plastic cover underneath
4. Insert the 24 V DC Back-up External Supply Option (D) in the Option Slot (E)
5. Mount the Cable Decoupling Plate (H)
6. Attach the Terminal Cover (G) and the Keypad (F) or Blind Cover.
External 24 V DC Supply
You can use the external 24 V DC supply as
low-voltage supply to the control card or any
option card installed. This enables full operation
of the Keypad (including the parameter setting)
without connection to line voltage.
External 24 V DC Supply
An external 24 V DC supply can be installed for low-voltage supply to the control card and any
option card installed. This enables full operation of the Keypad (including the parameter setting)
without connection to line voltage.
External 24 V DC supply specification:
Input voltage range ....................................................................................................... 24 V DC ±15% (max. 37 V in 10 s)
Max. input current .................................................................................................................................................................................... 2.2 A
Average input current for AF-650 GP or AF-600 FP ....................................................................................................... 0.9 A
Max. cable length ..................................................................................................................................................................................... 75 m
Input capacitance load................................................................................................................................................................... < 10 uF
Power-up delay .................................................................................................................................................................................... < 0.6 s
The inputs are protected.
Mechanical Installation (OPC24VPS)
Input voltage range:
24 V DC
±15%
(max. 37 V in 10 s)
Max. input current: 2.2 A
Max. cable length: 75 m
Input capacitance load:
110 uF
Power-up delay:
0.6 s
External 24 V DC supply specification
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - External 24 V DC Supply

1AF-650 GP & AF-600 FPTM 24 V External Supply InstructionFollow these steps:1. Remove the Keypad (F) or Blind Cover2. Remove the Terminal Cover (

Seite 2 - *MI33O122*

AF-650 GP & AF-600 FPTM 24 V External Supply Instructionimagination at workThe instructions do not purport to cover all details or variations in e

Kommentare zu diesen Handbüchern

Keine Kommentare